What the thermal protector blocks is the overheated chain of the gear reduction motor.

In continuous operation situations such as belt conveying, mixing, lifting, and packaging, gear reduction motor failures mostly manifest as excessive winding temperature. Overload, phase loss, voltage imbalance, mechanical jamming, and poor heat dissipation will eventually increase the current and accumulate heat. The insulation layer will first age and then degrade, and in severe cases, the winding will be short-circuited. The task of the thermal protector is to cut off the power supply before the temperature reaches the level of destroying the insulation; it does not wait for smoke to act, but simulates the heat accumulation process of the motor - the larger the overload current, the faster it will act, and a slight overload will allow it to last longer. This inverse time limit characteristic is exactly what motor protection needs. It should be noted that the thermal protector is only responsible for overload and over-temperature protection. Short-circuit protection must still be completed by a circuit breaker or a fuse. The combination of the two forms a complete circuit.

The principles and applicable occasions of three types of thermal protectors

Common thermal protection devices on site are divided into three categories, with different operating principles, response speed, accuracy and reset methods. When it is a gear reduction motor Selection, first look at their respective boundaries:

type

Action principle

Response speed

Protection accuracy

reset mode

Applicable occasions

bimetallic sheet

The difference in thermal expansion between the two metals causes the sheet to bend and open the contacts.

Second level (2~30 seconds, depending on tripping level)

Medium, temperature difference is about ±5℃

Manual or automatic optional

Medium and high power industrial motors, dust, moisture, vibration environment

PTC thermistor type

After the temperature rises, the resistance value increases suddenly, and the module is used to cut off the control loop.

milliseconds to seconds

higher

Mostly automatic recovery

Small model, embedded winding temperature measurement, frequent start and stop loads

electronic

Collect current and temperature sensors, and disconnect after MCU judgment

millisecond level

High, the temperature difference is about ±1℃

Manual or delayed automatic

Precision equipment, occasions requiring adjustable threshold and action recording

Motors equipped with small and medium-power gearboxes often use bimetallic thermal relays or thermal protectors embedded in the windings, which are simple in structure and resistant to vibration and dust. For precision working conditions that require accuracy and action recording, the electronic type can be selected; the PTC type is small in size and self-restoring, suitable for small models that frequently start and stop. Selection also depends on the installation location: the protector must be able to truly sense the motor temperature. The embedded winding type is closer to the actual thermal state than the external type installed in the control cabinet.

How to determine the setting current: based on the rated current of the motor

The setting current is the core parameter of the thermal protector, which determines the action boundary. In engineering, it is corrected based on the rated current of the motor and the nature of the load: I set = (1.0~1.2) × I N , where the rated current I N = P ÷ (√3 × U × cosφ × η). Please refer to the following table for the common correspondence relationships of 380V three-phase asynchronous motors:

Motor power (kW)

Rated current reference value (A)

Thermal protector setting range (A)

Remark

0.75

About 1.7

1.7~2.0

Select the smallest specification that covers the value

1.5

About 3.3

3.3~4.0

Take low values ​​for fans and water pumps

2.2

About 4.8

4.8~5.5

—

4.0

About 8.4

8.4~10

—

5.5

About 11.5

11.5~13

Frequent starts and stops can be slightly enlarged

7.5

About 15.5

15.5~18

The impact load is taken as 1.1~1.2 times

11

about 22

22 ~ 26

—

15

about 30

30~35

Heavy load start with 20-level tripping

Two reminders. First, give priority to reading the rated current on the motor nameplate, do not just rely on formulas to estimate; second, the nature of the load determines the correction coefficient - 1.0 to 1.05 times for steady loads such as fans and pumps, 1.1 to 1.2 times for impact loads such as crushers and compressors. In the case of frequent starts and stops and forward and reverse rotation, the correction coefficient can be slightly increased but generally does not exceed 1.2 times. There are also sites where the 10A motor is adjusted to 6A in order to 'protect the motor'. As a result, the equipment stops frequently before reaching the rated load. Repeated starts and stops increase the thermal stress of the windings. This kind of situation often indicates that the matching between the motor power and the reducer itself is too small, and the reducer output torque and reducer service coefficient should be recalculated instead of relying on adjusting the setting value.

Trip level and ambient temperature: Don’t let it trip accidentally at the start-up moment

The tripping level indicates the action time of the thermal protector at 7.2 times the set current: 10A level is about 2 to 10 seconds, 10 level is about 4 to 10 seconds, 20 level is about 6 to 20 seconds, and 30 level is about 9 to 30 seconds. For normal loads, choose 10A or level 10; for heavy load start-up and equipment that takes more than 10 seconds to start up, you should choose level 20 or even level 30, otherwise it will trip during the startup process. The full-load start of the belt conveyor and the start-up of the elevator with material fall into this category. It is appropriate to measure the actual start-up time of the belt conveyor reducer 、and elevator reducer before grading.

Ambient temperature also affects the operating point. The thermal protector should be in a temperature environment similar to that of the motor. If the motor is in a high-temperature workshop and the protector is installed in a control cabinet with a lower temperature, the action will be significantly slower and the protection effect will be compromised; conversely, in summer, when the temperature in the cabinet is obviously high, it will frequently trip by mistake. At this time, a model with ambient temperature compensation should be selected, or the setting value should be corrected according to the compensation curve. In the case of frequent inching, the repeated impact of the starting current will superimpose heat, and the setting value needs to be enlarged accordingly.

Reset after action: manual or automatic

After the thermal protector is activated, it must be reset before it can work again. The reset method is usually switched by a lever or screw. Both methods have their own applicable situations.

  • Manual reset : The reset button needs to be manually pressed before the contacts close again. It is suitable for occasions where it is required to find out the cause before starting the machine. This can avoid greater damage caused by repeated starts when the fault is not eliminated. The correct approach is to cut off the power and wait for complete cooling before pressing the reset button. Forced reset when cooling is insufficient will cause the protection to fail.

  • Automatic reset : The bimetal piece recovers automatically after cooling to the reset point. It is suitable for remote pumping stations, cooling fans and other equipment that are inconvenient to visit, but it should be combined with alarm output to let the personnel on duty know that an overload action has occurred. Most of the 'repeated starts and stops' seen on site are due to the protector being set to automatic reset.

  • Electronic reset : Most require manual reset or reset by PLC instructions. Some models support automatic restart with a delay of 3 to 10 minutes. The threshold is adjustable and the number of actions can be recorded for easy traceability.

After resetting, do not rush to run with load: first run without load to observe the current and temperature rise, confirm that the three-phase current is balanced and there is no abnormal heating of the terminals, and then load in stages of 30%, 60%, and 100%. If it operates again within a short period of time after resetting, it means that the fault has not been eliminated, and the machine should be stopped for troubleshooting instead of repeatedly pressing the reset button.

Checklist for frequent false jumps

Separate the reasons for the reducer’s heating from the electrical protection parameters. Misjumping usually occurs in the following items:

  1. The setting value does not match the actual current - measure the three-phase operating current with a clamp meter, compare it with the nameplate value and then reset.

  2. Ambient temperature mismatch - when the temperature inside the cabinet is significantly higher than the motor environment, correct it according to the compensation curve or switch to a compensation type.

  3. Poor terminal crimping - Failure to tighten the main circuit screws will cause the terminals to heat up, and the heat will be conducted to the bimetal piece causing malfunction. Retighten to the specified torque.

  4. Insufficient auxiliary contact capacity - using 95-96 to directly drive a large contactor coil will ablate the contacts, so an intermediate relay should be added for conversion.

  5. Multiple motors share a set of protection - when a single motor is overloaded, the total current does not change significantly and the protection does not operate. In principle, one motor has one set of protection.

  6. Real mechanical failure - bearing jamming, abnormal gear meshing, and sudden increase in load will cause the current to really increase. At this time, the reducer bearing replacement cycle, lubrication status, and coupling alignment should be checked, and reducer repairs should be arranged if necessary.。

  7. The protector itself is aging - bimetallic fatigue, PTC resistance drift due to moisture, and contact oxidation will all cause the action point to shift. Simulated action tests should be done regularly, and if it fails, it should be replaced in time.

Conclusion: Protection parameters and mechanical status should be viewed together

The setting of the thermal protector is not complicated: the setting current is corrected according to the load based on the nameplate rated current, the tripping level is selected according to the start-up time, the reset method is determined according to whether it is manned or not, and then the details of terminal crimping, ambient temperature and contact capacity are solid, and the overload protection of the gear reduction motor is basically reliable. On the other hand, if the protector operates frequently but no problem is detected on the electrical side, it often indicates that there is a real overload on the mechanical side - this is especially common for packaging machine reduction motors , mixing and conveying equipment, and needs to be solved at the maintenance level. Hangzhou Weigao Transmission's product line covers cycloidal pinwheel reducers, hardened cylindrical gear reducers, worm gear reducers, planetary reducers and coaxial reducers. Gear reduction motors and protection solutions can be matched according to working conditions; as a reducer manufacturer and Hangzhou reducer manufacturer , Weigao Transmission provides free calculations, gear reduction motor price and delivery consultation, and supports customization of reducers based on drawings and samples . We welcome reducer consultations , and engineers will be available at 24 A complete Selection plan and quotation will be issued within hours.